Balometer Air Flow Capture Hood

  • NIST Traceable Calibration Certificate
  • 23 to 2530 cfm (40 to 4300 m3/h) measuring
    range
  • Simultaneously measures and displays
    airflow, temperature and humidity
  • Displays the direction of the airflow as we ll
    as the velocity
  • Removable handheld micromanometer with
    Bluetooth® wireless capability (Model 6715)
  • Advanced storage feature allows you to
    store multiple measurements under a
    single ID#Lightweight design makes one-person
    setup and use easy
  • Six hood sizes make it easy to pick one
    that fits your duct size
  • Built-in back pressure compensation
    ensures accuracy for large volumetric
    flow measurements

micromanometerTABmasterTM is the perfect tool for accurate supply and return airflow measurements. Interchangeable hoods make it a snap to sample the air for any duct size. The unit is lightweight and easy to handle. The full color screen can be tilted so it's at
the optimal viewing angle at any height.
Model 6715 includes, in addition, a removable handheld micromanometer (6700) with Bluetooth® wireless capability. This can be uses with pitot tubes and a Velocity Grid to measure air velocity.
Applications include HVAC testing adjusting and balancing, air volumetric flow measurements through registers, diffusers and grills, measureing supply and return airflow and air velocity in ducts.

Air Flow capture Hood Specifications

Function Parameter Model 6710 Model 6715
Airflow Range
Accuracy
Resolution
23 to 2530 cfm (40 to 4300 m3/h)
±3% of readings ± 8 m3/h
1 m3/h
Air Velocity Range
Accuracy
Resolution
n/a 0.15 to 40 m/s (with pitot tube)
0.15 to 15 m/s (with Velocity Matrix)
+/- 3% of reading +/- 0.05m/s
0.01 m/s (<9.99m/s), 0.12 m/s (>10.0m/s)
Temperature Range
Accuracy
Resolution
  -32 to 122°F (0 to 50°C)
+/- 1.0°F (0.5°C)
0.1°C
Humidity Range
Accuracy
Resolution
  0 to 100 %RH
+/- 3.0 %RH
0.1 %RH
Interface USB USB Bluetooth
Data logging 3000 record 8000 records
Power supply AA batteries and AC adapter
Hood Dimensions 2 x 2 ft (610 x 610 mm), 1 x 4 ft (305 x 1220 mm)
2 x 4 ft (610 x 1220 mm), 3 x 2 ft (915 x 610 mm), 3 x 3 ft (915 x 915 mm), 500 x 500 mm
Weight 7.9 lbs (3.6 kg)

Micromanometer Specifications

Function Parameter Model 6710 - this meter is included with the 6715 kit
Air Velocity Range
Accuracy
Resolution
0.15 to 40 m/s (with pitot tube)
0.15 to 15 m/s (with Velocity Matrix)
+/- 3% of reading +/- 0.05m/s
0.01 m/s (<9.99m/s), 0.12 m/s (>10.0m/s)
Pressure Range
Accuracy
Resolution
-2500 to 2500 Pa
1.5%±0.25Pa
0.001 Pa
Temperature Range
Accuracy
Resolution
-32 to 122°F (0 to 50°C)
+/- 1.0°F (0.5°C)
0.1°C
Humidity Range
Accuracy
Resolution
0 to 100 %RH
+/- 3.0 %RH
0.1 %RH
Interface USB Bluetooth
Data logging 8000 records
Power supply AA Batteries and AC Adapter

Ordering information

Model Description US $  
6710 Meter , Standard hood (2 x 2ft), PC communication cable, Data processing software, Operational manual, Ballistic Nylon Carrying case, NIST TRACEABLE CALIBRATION certificate $2480.00
6715 Portable Micro Manometer (Model 6700), Standard hood (2 x 2ft), PC communication cable, Data processing software, Operational manual, Carrying case, NIST TRACEABLE Calibration certificate $3280.00
671008 Tripod Stand $800.00
671001 velocity Grid $380.00
670012 Pitot Tube 12" $125.00